Creating a Rule-based Indicator Template

A rule-based indicator is an indicator where the current state is determined by a rule rather than by a direct reading. The rule is made up of clauses based on the current state of other indicators. The rule allows APM to warn you of the existence of a potential problem.
Rule-based indicator templates include a rule based on the states of other indicator templates. When you create the asset indicator from the rule-based indicator template, you must update the rule with the appropriate asset indicators.
Note: On indicator templates, you can only use other indicator templates in your rule. When you use the template to create an asset indicator, you must reset the rule so that it uses the correct asset indicators.

To Create a Rule-based Indicator Template

1.
Select the site’s Inspection Management view, Indicators tab.
2.
Select the Templates tab. By default, the table lists the indicator templates for the site and above.
3.
Click New. The Indicator template window appears.
4.
On the Properties view, General tab:
Select a rule-based indicator type from the Indicator type list. When you select a rule-based indicator type, the Type of value box says “Rule-based.” The window changes to reflect the value type.
On the Collection tab, “Evaluated based on a rule” appears in the Collection method box.
5.
On the Collection tab, you can enter values that determine how often readings are expected and the next collection date. You can also enter information to make it easier to select this indicator when adding indicators to a work order task or standard task, when copying indicators to another asset, when setting up dynamic inspection routes, or when implementing reliability programs.
If you are creating the indicator from a strategy development analysis (MTA2, RCM2, RBI, CPR), the searching values (frequency, regulatory frequency, trade, operating condition, maintenance group, and technology) are automatically copied from the associated action plan, if the analysis’ indicator settings allow it. In this case, you need only verify the values.
Note: Any changes that you make to the searching values are not copied to the indicator’s associated action plan.
Review and select values, as appropriate:
Tip: If the technology is linked to an asset type that is used to collect indicator readings, you can identify the measurement device on indicator readings and checksheets.
6.
To specify the months during which readings should be taken, select the Seasonal tab. Click This indicator is collected seasonally and select the starting and ending dates. For example:
Reading due dates will reflect the seasonal settings.
7.
Select the Description tab to enter more information about the indicator.
8.
Select the Rule tab.
9.
10.
From the Indicator to use list, select an indicator template to use for the clause.
11.
If available, in the Trigger based on list, select whether the clause is evaluated based on the state or the value of the indicator. If you cannot change the setting in this list, it is because the selected indicator has either only states (for example, descriptive) or only values as readings (for example, numeric without states).
12.
In the Operator list, select how the clause is evaluated.
13.
14.
To save the clause and close the dialog, click OK. To add another clause, repeat steps 9 to 13.
15.
Select an alarm for the rule in the Type of alarm to raise if the rule is true list.
16.
If necessary, you can change the Required Proximity of the rule inputs. By default, APM sets this to be 1.00 day. If any of the inputs are entered into the system outside of the required proximity time, APM will not evaluate the rule.
For example if the required proximity is 1.00 day and indicator A records a reading at 8:00 am on Monday, and indicator B records a reading at 12:00 noon on Tuesday, the rule would not be evaluated.
17.
Tip: To create asset indicators using this template, see Creating Indicators from Indicator Templates.